HD2-DM-A_Fieldbus Power Hu
简介:Comprehensive diagnostics for fieldbus physical layer and power supply Plug-in Module for the FieldConnex Power Hub Precise measurements through passive circuits For commissioning, online monitoring and troubleshooting For FOUNDATION Fieldbus H1 and PROFIBUS PA Installation in Zone 2/Class I, Div. 2 System state and fault indication via LEDs Display of data in the safety of the control room...
Brand
Made In
Modle PXF2627
Disctount
PassionTech Ord OrderNum Product Name Price RMB Brand  
该文章系原厂商文章翻译,不通之处请参考原文

 

  • Comprehensive diagnostics for fieldbus physical layer and power supply
  • Plug-in Module for the FieldConnex Power Hub
  • Precise measurements through passive circuits
  • For commissioning, online monitoring and troubleshooting
  • For FOUNDATION Fieldbus H1 and PROFIBUS PA
  • Installation in Zone 2/Class I, Div. 2
  • System state and fault indication via LEDs
  • Display of data in the safety of the control room
  • Automatic setup of diagnostic system
  • Full software integration into DCS and PAM possible

    Datasheet excerpt: Technical data of HD2-DM-A

Supply
Rated voltage 19.2 ... 35 V
Rated current 110 ... 30 mA
Power loss max. 2 W
Fieldbus interface
Number of segments 4
Fieldbus type FOUNDATION Fieldbus/PROFIBUS PA
Rated voltage 9 ... 32 V
Indicators/operating means
LED PRI PWR green: on, primary bulk power supply connected
LED SEC PWR green: on, secondary bulk power supply connected
LED Seg 1...4 yellow: bus activity; red 2 Hz flashing: alarm; red: hardware error
Fault signal VFC alarm 1 A, 50 V DC, normally closed
DIP-switch diagnostic address 1...247, binary coded
Electrical isolation
Fieldbus segment/Fieldbus segment functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Fieldbus segment/Supply functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Directive conformity
Electromagnetic compatibility  
  Directive 2004/108/EC EN 61326-1:2006
Standard conformity
Electromagnetic compatibility NE 21:2006
Protection degree IEC 60529
Shock resistance EN 60068-2-27
Vibration resistance EN 60068-2-6
Ambient conditions
Ambient temperature -40 ... 60 °C (-40 ... 140 °F)
Storage temperature -40 ... 85 °C (-40 ... 185 °F)
Relative humidity < 95 % non-condensing
Shock resistance 15 g 11 ms
Vibration resistance 1 g , 10 ... 150 Hz
Corrosion resistance acc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Connection type Motherboard specific
Core cross-section Motherboard specific
Housing material Polycarbonate
Housing width 18 mm
Housing height 106 mm
Housing depth 128 mm
Protection degree IP20
Mass approx. 100 g
Mounting motherboard mounting
Mating cycles 100
Data for application in connection with Ex-areas
Statement of conformity TÜV 04 ATEX 2500 X
  Group, category, type of protection, temperature class Ex-HexagonII 3G EEx nA IIC T4
Directive conformity  
  Directive 94/9/EC EN 60079-15:2003
International approvals
FM approval CoC 3024816, CoC 3024816C
  Approved for Class I, Division 2, Groups A, B, C, D, T4 / Class I, Zone 2, AEx/Ex nA IIC T4
Certificates and approvals