The PicoLog CM3 Current Data Logger is a compact, easy–to–use data logger for measuring the power consumption of buildings and machinery.
- 3 channel current data logger
- Suitable for single or three–phase alternating currents
- Low conversion time
- High resolution and accuracy
- No power supply required
- USB and Ethernet interfaces
- Run multiple units on a single PC
High resolution and accuracy
The 24–bit resolution of your PicoLog CM3 ensures that you can detect the smallest changes in current, while with accuracy within ±1% you know that can rely on your measurements.
Take measurements at the speed you want
With a conversion time of just 720 ms per channel your PicoLog CM3 is capable of logging fast changes in current, but we know that in order to identify problems you may also need to monitor currents over long periods, so with a PicoLog CM3 you can take measurements at a speed to suit your application — whether that’s every few seconds, minutes, hours or even every few days.
Monitor currents from your desktop to the other side of the world
With both USB and Ethernet interfaces your PicoLog CM3 can be used in a variety of situations. If you need a portable instrument that can be used at various locations and is fast to set up and use, simply connect your laptop to the PicoLog CM3 by USB. Need to monitor a situation over a period of hours or days, or from a remote location? Plug your PicoLog CM3 into a spare port on your network and then access it remotely either from your LAN or over the internet — thanks to Power over Ethernet (PoE) technology you don’t even need a separate power supply.
Software that does what you need it to
Your PicoLog CM3 Current Data Logger is supplied with PicoLog data logging software. With PicoLog you can collect up to one million measurements, analyse them and then display the results in spreadsheet and graphical formats. You can view the data both in real–time as you are collecting the measurements, or you can save the data and view it later. You can also set alarms to warn you if the current goes above or below a set value.
A software development kit (SDK) is also supplied. The SDK contains a range of software drivers and example code that you can use to write your own software or to use your PicoLog CM3 with third–party software such as LabVIEW.
Both PicoLog and the SDK are provided free of charge and updates can be downloaded for free.
Create your own data acquisition system
With a PicoLog CM3 you can measure three separate currents. If that’s not enough, using PicoLog software you can add a further 19 PicoLog CM3s to your PC — enabling you to simultaneously measure up to 60 currents. Alternatively, you can mix–and–match Pico data loggers to create your own custom data acquisition system. For example, you may want to monitor how the opening and closing of doors affects the temperature and electricity usage of a cold room. You could do this with a PicoLog CM3 and a PT-104.
The only current data logger you need
With three channels, high accuracy and low noise, a PicoLog CM3 Current Data Logger is ideal for recording data from both single–phase and three–phase AC supplies. While its compact size, together with having both USB and Ethernet interfaces, gives you a versatile instrument that you can take with you or leave on–site for remote monitoring.
Whether you need to monitor three–phase motors and generators, measure the current consumption ofHVAC systems or simply monitor the current consumed around the home or office, a PicoLog CM3 Current Data Logger is the only current data logger you need.
Specifications
PicoLog CM3 Current Data Logger Specifications |
Number of channels |
3 |
Range (voltage input) |
0 to 1 V AC RMS |
Accuracy (voltage input)
< 200 mV RMS
< 1 V RMS |
±1%
±2.5% |
RMS Noise |
60 µV |
Resolution |
24 bit |
Conversion time per enabled channel |
720 ms |
Voltage input |
1 V RMS, 20 Hz to 1 kHz |
Input connectors |
4 mm sockets |
Input impedance |
>1 MΩ, AC coupled |
Overvoltage protection |
±30 V DC |
PC Requirements |
Minimum |
Processor: 1 GHz
Memory: 512 MiB
Free disk space: 32–bit: 600 MB, 64–bit: 1.5 GB
Operating system: 32– or 64–bit edition of Microsoft Windows XP (SP3), Vista, Windows 7 or Windows 8 (not Windows RT)
Ports: USB 1.1 compliant port or Ethernet |
Recommended |
Processor: 1 GHz
Memory: 512 MiB
Free disk space: 32–bit: 850 MB, 64–bit: 2 GB
Operating system: 32– or 64–bit edition of Microsoft Windows XP (SP3), Vista, Windows 7 or Windows 8 (not Windows RT)
Ports: USB 2.0 compliant port or Ethernet |
Environmental |
Operating environment
Temperature range
Humidity range |
0 °C to 50 °C (20 °C to 28 °C for stated accuracy)
20% to 80% RH, non–condensing |
Storage environment
Temperature range
Humidity range |
-20 °C to +60 °C
5% to 95% RH, non–condensing |
Physical Properties |
Dimensions |
184 x 135 x 36 mm (approx 7.2 x 5.3 x 1.4 in)
|